Basic concept¶
System Eneratptor is designed to take predefined actions in response to events in the surrounding world. The logic system is designed to be easily calibrated and managed. In addition to its predefined logic it allows the human administrator (through HMI) to reverse any automated or scripted decision and to execute any of the predefined actions, thus allowing the operator to tweak the system according to her best judgement.
The logic of the system consists of the following concepts:- Device maneger
- Mailbox
- Decision making software
- Predefined action list
- Action
- Human Machine Interface
The basic idea behind this design is modularity. Eneraptor supports any device and can execute any action as long as the driver follows our standard. In this scenario we [the eneraptor designers] expect the device manufacturer (ie air conditioning unit) at least two supply two programs : the device manager and the action program. If there are several actions supported by the device, we expect each to be a standalone program or all actions to be in a single program targeted by different command line arguments.
Concepts described in detail¶
Device manager¶
Device manager is basically a program. The eneratptor system doesn't know anything about it, the only crucial part is the driver-mailbox communication through witch data is supplied. More about date in the message specification. The device manager has to know how to reach the mailbox and how to correctly format the message. The device manager does not receive any confirmation from the message recipient.
This driver is not necessarily the same software which is supplied by the manufacturer, it is only a program that communicates with the eneratpr Mailbox.
Mailbox¶
Mailbox is a bridge between the device managers and the decision making software. It is a buffer of messages that the decision making software can read at its own pace.
The design of the mailbox and message structure is still open to debate; all input is welcome!
The mailbox should be event driven, meaning no periodic checking is necessary. The device manager will signal the control program which will in turn read the shared variable for data.
Decision making software¶
Decision making software is the key mechanism of the eneraptor project. It brings all other components together to ensure all conditions set by (human) operators are met.
The decision making software continuously checks the mailbox for new messages. If any new info is read the software compares it with all the predefined conditions (see predefined action list). If a condition is met, the action is executed. If several conditions are met, all co-responding actions are executed.
This (very elegant) main loop is always executing, however it can be halted by the Human Machine Interface. When this happens the loop still executes, however all but the messages originating from HMI are ignored.
Predefined action list¶
Predefined action list is a list of all the conditions and co-responding actions entered to the system. It is implemented as a non-ordered list of structures containing the information:
- Input device ID
- Corner value
- Comparison operator
- Action to be executed
The list is saved in a csv/xml file. It is initialized with on the Decision Making Software program startup and then periodically refreshed, insuring no restart is required when additional rules are entered.
Action¶
Action is a program path and program argument pair, thus allowing the Decision making software to execute it.
There are several rules for the Action developers:
- The Action program must be executable through command line,
- The Action program must not expect human interaction,
- The Action program must terminate in a deterministic time,
Outside of this very general rules the Action developers have no limitations in writing the Action programs.
Communication and message formats¶
The logic component uses three types of messages to connect to other parts of the Eneraptor system. They are the following:
- The message for communication with device manager -> XML
- The message for communication with HMI -> XML
- The message for logging (via syslog) -> formatted plain text
These messages are then transported over the network to their destination.
- The Logic -> device manager communication uses IP sockets to relay messages.
- The Logic <--> HMI communication uses UDP communication to relay messages.
- The Logic <--> Logging service uses syslog's built in mechanism for relaying the messages to their destination.
The logic <--> device manager message¶
The device manager logic is twofold: when the device manager signals new available data, it is read from a shared variable (encapsulated within a monitor). The IP socket is used for the reverse connection, when the HMI request a certain value which has to be read. When that happens a request message is sent. The messaging thread blocks until an answer is received. The response is then transformed to Logic -> HMI message and sent to HMI.
The syntax of the request message is irrelevant since the there aren't several data points to choose from. The response however should be a single double value (defined with IEEE 754).
Questions:- Will there ever be a device manager with several data points available for reading?
- The named pipe option was considered however I prefer the IP socket protocol. The main reason behind this decision is that a named pipe can only be open for reading or writing thus complicating the programming somewhat.
The logic <--> HMI message¶
Alex B. proposal:
There should exist three types of messages used for communication between the logic and HMI, depending on how should the logic react after receiving a message:
- Type1: HMI requests for some information; logic replies.
- Type2: HMI requests for a change in logic's configuration; logic reacts; logic sends a message confirming changes have been succesfully (or unsucsessfully) applied.
- Type3: HMI wants to add or change a new acion
The first message type from HMI could looke like this:
<hmi-request> <device-stat> <device id="Thermometer_01" /> <device id="Moisture_meter" /> </device-stat> <config-stat> <config id="startup_time" /> <config id="logging-enabled" /> </config-stat> </hmi-request>
And the logic's response could look like this:
<logic-response> <device-stat> <device id="Thermometer_01"> <value>24</value> </device> <device id="Moisture_meter"> <error type="device_controller_returned_1" /> </device> </device-stat> <config-stat> <config id="startup_time">08:25:22 22/12/2010</config> <config id="logging-enabled">true</config> </config-stat> </logic-response>
The second type of HMI's request could look like this:
<hmi-request> <config> <config id="logging-enabled">false</config> </config> </hmi-request>
And the response could look like this:
<logic-response> <config> <config id="logging-enabled">success</config> </config> </logic-response>
The third message type from HMI could look like this:
<hmi-request> <todo> </hmi-request>
And the response could look like this:
<logic-response> <todo> </logic-response>
Of course all three types of messages could be joined in a single XML file if this would be useful (?).
The logic -> logging¶
The logic uses syslog to save a plain text message to the database. However the message has to be formatted, so the information can be extracted by the Statistical Data Analysis Software (Archive and statistics.
The archiving can be initiated for the following reasons:- Type1: New data was sent by the device manager,
- Type2: Action was taken due to the read changes in the observed world,
- Type3: Action was initiated by the system administrator via HMI.
The reason for the archiving has to be visible in the message. Thus the first byte of the message is reserved for the type of the message. The rest of the message is conditioned by the type. The first byte is followed by:
Type1¶
- The new data received, saved in a single double value (IEEE 754).
Type2¶
- The action taken (id of the action saved in a single short int value)
Type3¶
- The action taken (id) followed by the system administrator id.
Configuration¶
The configuration consists of a XML file, which is read on startup. The XML file should look like this:
<todo>
The configuration can also be modified by the HMI. When that happens the XML configuration file has to be modified to reflect the new changes.
The interfaces¶
The following interfaces have to be defined by the extern components for them to be seen as a valid Eneraptor component:
<todo>
Updated by David Božjak about 14 years ago · 16 revisions